A kW-scale, 24-hour continuously operational, radiative sky cooling system [electronic resource] : Experimental demonstration and predictive modeling

 0 Người đánh giá. Xếp hạng trung bình 0

Tác giả:

Ngôn ngữ: eng

Ký hiệu phân loại: 621.3 Electrical, magnetic, optical, communications, computer engineering; electronics, lighting

Thông tin xuất bản: Oak Ridge, Tenn. : Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy, 2019

Mô tả vật lý: Size: p. 586-596 : , digital, PDF file.

Bộ sưu tập: Metadata

ID: 255639

 With the advancement in sub-ambient cooling of water during daytime under the sun with scalable-manufactured radiative cooling metamaterials, the challenge for applications lies in design and building of large-scale radiative cooling systems. Here, we present a kW-scale, 24-hour continuously operational, radiative sky cooling system, with both experimental study and detailed modeling. We first quantitatively show how water flow rate directly affects the system cooling power and inversely affects the water temperature drop. A day-and-night stagnant (flow rate = 0 L/(min�m<
 sup>
 2<
 /sup>
 )) water cooling test of the system shows a consistent sub-ambient water temperature drop of 5?7 �C. A daytime cooling test of the system at a low flow rate of 0.227 L/(min�m<
 sup>
 2<
 /sup>
 ) yields a maximum sub-ambient temperature drop of 4.0 �C with an average net cooling power of around 80 W/m<
 sup>
 2<
 /sup>
 . Further modelling for a typical metrological year (in Phoenix, Arizona) shows that the system could generate as much as 350 kWh cold (or 26 kWh/m<
 sup>
 2<
 /sup>
 ) with a sub-ambient temperature drop of 4?5 �C at a low flow rate of 0.1 L/(min�m<
 sup>
 2<
 /sup>
 ) during a typical summer month. The cold generated could be used to assist AC systems in regions or seasons with high ambient temperatures.