CGI for Impedance Characterization of Inverter-Coupled Generation [electronic resource]

 0 Người đánh giá. Xếp hạng trung bình 0

Tác giả:

Ngôn ngữ: eng

Ký hiệu phân loại: 628.3 Sewage treatment and disposal

Thông tin xuất bản: Washington, D.C. : Oak Ridge, Tenn. : United States. Dept. of Energy. Office of Energy Efficiency and Renewable Energy ; Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy, 2019

Mô tả vật lý: Size: 3 MB : , digital, PDF file.

Bộ sưu tập: Metadata

ID: 258068

This presentation provides an overview of impedance characterization of inverter-coupled generation using the 7 MVA/13.2 kV grid simulator (controllable grid interface) at the National Wind Technology Center of NREL. The presentation shows how sequence impedance responses of multi-megawatt inverters and wind turbines are measured using the grid simulator. Applications of the measured impedance responses for the evaluation of dynamic interactions and high-fidelity model validation are demonstrated. The presentation also shows application of large-signal impedance theory for the prediction of harmonics generated by subsynchronous resonance (SSR) of DFIG-based Type-III wind turbines with series-compensated transmission lines. Finally, a new method for impedance-based characterization of power system frequency response is presented to enable real-time estimation of system inertia and primary frequency response (PFR), and to support control design for frequency support by inverter-coupled generation.
Tạo bộ sưu tập với mã QR

THƯ VIỆN - TRƯỜNG ĐẠI HỌC CÔNG NGHỆ TP.HCM

ĐT: (028) 71010608 | Email: tt.thuvien@hutech.edu.vn

Copyright @2020 THƯ VIỆN HUTECH